Trung tâm điều khiển 8 zones COFEM CLVR08Z
- CLVR Control panel up to 8 zones.
- 2 supervised sounder outputs, delayed from 0 to 10 minutes, and protected by a fuse.
- 1 alarm output through a dry contact NO/NC (normally open/ normally closed).
- 1 fault output through a dry contact NO/NC (normally open/ normally closed).
- 2 auxiliary outputs 30V/DC supervised and protected by a fuse to feed external (magnetic fire doors, sounders, etc).
- Available testing mode to facilitate the quick and easy verification of the sensors and call points.
- It allows to configure the open line, alarm detector and alarm call point threshold, to adjust to the operation with other detectors.
- It allows to configure the last detection zone as a supervision input of a external protection fire system with a fault indication.
- Metallic chest with frontal bolted door, 4 predrilled of 28 mm and one rectangular else of 140 x 20 mm for electric wiring and space for 2 batteries of 7Ah.
- RS485 MODBUS protocol on-demand.
- Possibility of software ON-LINE on PC using MODBUS functionality.
- CONTACTID on-demand.
- Certified according to EN 54-2 & EN 54-4 standards and CE mark.
Đặc tính kỹ thuật
Model | CLVR 8 |
Input voltage | 110/230VAC 50/60Hz |
Output voltage | 21V Nominal |
Maximum consumption | 70 VA to 230 V/AC |
Batteries | 2x12V7 Ah SLA |
Max. voltage 30V output | 0,75A/ 1,50A |
Battery charger | 500 mA 27 V/DC 20ºC |
Devices per zone | 32 |
Control panel power supply | 2,2 A |
Maximum current per zone | 2 mA (standby) |
End of line capacitor | 4 K7 |
Sounder output voltage | 30V/DC 2 A |
Fault output | Yes, dry contact |
Environmental conditions | -10ºC +50ºC |
Size | 363 x 331 x 96 mm |
Weight (without batteries) | 4,3 Kg |
Standar | EN 54-2, EN 54-4&EN 12094-1 |
Sounder output fuse S1 | 1A/ 1,85A Autoreset |
Sounder output fuse S2 | 1A/ 0,75A Autoreset |
- Bảo hành: 12 tháng.